SPECIFICATIONS: INTERNAL
The RINCON XP comes standard with 120/277/347V input and is designed to perform in applications where the environment would punish any other unit. Lead acid battery is standard, Ni-Cad optional, provides a minimum emergency duration of 90 minutes. The solid state, high efficiency, dual rate charger provides precise float voltage control and low voltage disconnect protection.
SPECIFICATIONS: EXTERNAL
The RINCON XP series is constructed from .100” thick, heavy duty cast aluminum. Tamper resistant screws are standard and ensure the integrity of the battery unit. The RINCON series comes standard in an industrial gray color although custom color options are available upon request. The RINCON comes standard with an LED status indicator and test switch under the lens. The lens is constructed from a vandal resistant polycarbonate for maximum durability. Lamp and reflector assemblies are offered in a fully adjustable, high output MR16 halogen or LED configuration. Universal mounting pattern and key hole slots are cast into the backplate. Stainless steel mounting straps are supplied for surface mounting.
HAZARDOUS
The RINCON XP series is approved for use in Class I Division 2, Groups ABCD, Class II Divisions 1 & 2, Groups EFG: T coded T4A, T3B, T3A, T2D, T2A, or T1.
SPECIFICATIONS: ELECTRICAL
BATTERY: The RINCON XP is designed with a maintenance free, sealed valve regulated lead acid battery that provides a minimum emergency duration of 90 minutes. Recharge time of the battery is less than forty-eight [48] hours. An optional Nickel-Cadmium battery is available. The maximum battery operating temperature is +40°C and the minimum is +10°C.
CIRCUIT: The RINCON XP utilizes a high-efficiency two stage charger providing precise float voltage control with low voltage disconnect protection. All components used in the circuitry are temperature compensated. The charger also has brownout and short circuit protection. Charger status is easily determined via a dual diagnostic LED display which indicates AC/ON and high charge. A magnetic test switch allows maintenance personnel to quickly determine the operational status of the unit and lamp load.
SPECIFICATIONS: MECHANICAL
The RINCON XP is constructed from a durable, fully gasketed die-cast aluminum housing rated for NEMA 4X and IP66. Stainless steel mounting straps are supplied for surface mounting. These connectors allow for a large gauge of wire to be used, increasing the flexibility or installation. The RINCON XP is supplied standard in a durable gray powder coat, baked finish. Other colors are available, including color matching, please specify. CSA 22.2 No. 141 Performance Certified.
SANITATION LISTED (SL)
The RINCON XP is sanitation approved. The Intertek verified splash zone listing is equivalent to the NSF Standard 2, meeting the rigorous sanitation, electrical safety and performance standards of food service environments.
WARRANTY
The RINCON XP comes with a 3-year factory warranty. Deliberate damage, misuse, improper installation effectively cancel the warranty.
FME Lighting | 18585 Coastal Highway | Unit 10 PMB 104 | Rehoboth Beach Delaware, 19971
877-234-8460 | Fax: 302-650-1901 | info@fmelighting.com